YAVV
0,6/1 kV Single Core Power Cable with AI. Conductor, PVC Ins. PVC Jacket
YAVV (NAYY-RM) 1 (SINGLE) CORE
CONDUCTOR SHAPE and CONDTRUCTION
APPLICATION
- Indoor or outdoor installations, where there is no mechanical damage risk
- Maximum continious normal operating temperature: 70C
- Maximum short circuit temperature: 250C
- Standard: IEC 60502-1
- Cables for rated voltages of 1 kV (Um=1,2 kV)
Nominal Area
of Conductors |
Min. No. of Wires
in Phase Conductor |
Nominal Insulation
Thickness |
Nominal Outer
Sheath Thickness |
Overall Diameter
(approx.) |
Cable Unit
Weight (approx.) |
DC Resistance 20C’de |
Current Carrying Capacity | |||
---|---|---|---|---|---|---|---|---|---|---|
In Air | Under Ground | |||||||||
Flat | Trefoil | Flat | Trefoil | |||||||
mm2 | mm | mm | mm | kg/km | ohm/km | A | A | A | A | |
1 İletken | ||||||||||
1×25 | 6 | 1,20 | 1,4 | 11,1 | 190 | 1,200 | 110 | 87 | 160 | 106 |
1×35 | 6 | 1,20 | 1,4 | 12,1 | 230 | 0,868 | 135 | 107 | 193 | 127 |
1×50 | 6 | 1,40 | 1,4 | 13,7 | 290 | 0,641 | 166 | 131 | 230 | 151 |
1×70 | 12 | 1,40 | 1,4 | 15,5 | 380 | 0,443 | 210 | 166 | 283 | 185 |
1×95 | 15 | 1,60 | 1,5 | 17,5 | 490 | 0,320 | 259 | 205 | 340 | 222 |
1×120 | 15 | 1,60 | 1,5 | 18,7 | 580 | 0,253 | 302 | 239 | 389 | 253 |
1×150 | 15 | 1,80 | 1,6 | 21 | 720 | 0,206 | 345 | 273 | 436 | 284 |
1×185 | 30 | 2,00 | 1,7 | 23,4 | 880 | 0,164 | 401 | 317 | 496 | 313 |
1×240 | 30 | 2,20 | 1,8 | 26,1 | 1100 | 0,125 | 479 | 378 | 578 | 375 |
1×300 | 30 | 2,40 | 1,8 | 28,7 | 1300 | 0,100 | 555 | 437 | 656 | 419 |

YAVV
0,6/1 kV Single Core Power Cable with AI. Conductor, PVC Ins. PVC Jacket
YAVV (NAYY-RM) 4 CORE
CONDUCTOR SHAPE and CONDTRUCTION
APPLICATION
- Indoor or outdoor installations, where there is no mechanical damage risk
- Maximum continious normal operating temperature: 70C
- Maximum short circuit temperature: 250C
- Standard: IEC 60502-1
- Cables for rated voltages of 1 kV (Um=1,2 kV)
Nominal Area
of Conductors |
Min. No. of
Wires in Phase Conductor |
Nominal Insulation
Thickness |
Nominal Outer SteathThickness |
Overall Diameter
(approx.) |
Cable Unit Weight
(approx.) |
DC Resistance at 20C |
Current Carrying
Capacity |
|
---|---|---|---|---|---|---|---|---|
In air | Under ground | |||||||
mm2 | mm | mm | mm | kg/km | ohm/km | A | A | |
4 Conductor | ||||||||
4×16 | 6 | 1,00 | 1,80 | 21,00 | 640 | 1,910 | – | – |
4×25 | 6 | 1,20 | 1,80 | 25,00 | 620 | 1,200 | 82 | 102 |
4×35 | 6 | 1,20 | 1,80 | 27,00 | 1100 | 0,868 | 100 | 123 |
4×50 | 6 | 1,40 | 1,90 | 31,00 | 1480 | 0,641 | 119 | 144 |
4×70 | 12 | 1,40 | 2,10 | 36,00 | 1980 | 0,443 | 152 | 179 |
4×95 | 15 | 1,60 | 2,30 | 41,00 | 2600 | 0,320 | 186 | 215 |
4×120 | 15 | 1,60 | 2,40 | 45,00 | 3100 | 0,253 | 216 | 245 |
4×150 | 15 | 1,80 | 2,50 | 50,00 | 3800 | 0,206 | 246 | 275 |
4×185 | 30 | 2,00 | 2,70 | 56,00 | 4700 | 0,164 | 285 | 313 |
4×240 | 30 | 2,20 | 2,90 | 62,00 | 6900 | 0,125 | 338 | 364 |